FS#889 — FS#4921 — Row 06xxx

Attached to Project— Dedicated servers
Incident
Roubaix 1
CLOSED
100%
During the periodic test of the generators at RBX1, a default
has impacted the room 6.

We still do not know the origin of the problem on the inverter
supllying this room. our team is working currently for the
restarting of the servers.

The datacenter is now supplied by the generators.
We are waiting for the arrival of the Chloride
technicians to identify the problem.

Date:  Sunday, 12 December 2010, 19:34PM
Reason for closing:  Done
Comment by OVH - Tuesday, 07 December 2010, 15:21PM

I took the decision to switch again on EDF with a probable
cut of the room. That cut occured. The inverter is dead.
The constructor Chloride is on the way to repair it.

We change the procedures for the test of the generators that
we do every month.

The new procedures must take in consideration the fact that the inverter
can crash and not get back.


Comment by OVH - Sunday, 12 December 2010, 19:13PM

Despite the intervention of the manufacturer, the inverter is always visibly defective.
During the electrical interruption. https://status.ovh.net/?do=details&id=890 We have again lost the room's supply.

Works concerning the UPS:
https://status.ovh.net/?do=details&id=906